NCC 2025’s New 98th Percentile Rule for J1V3: What Commercial Projects Need to Know Now
NCC 2025 has introduced a new compliance check for commercial buildings, and it’s already reshaping how J1V3 modelling gets done. The 98th percentile rule sets a hard limit on how far a proposed building’s zone-by-zone heating and cooling loads can drift from the reference building — not just on average, but at the demanding end of the year. For anyone running or relying on J1V3 assessments, understanding this new check now is the difference between a model that sails through and one that needs to be reworked from scratch.
What Is the 98th Percentile Rule?
The 98th percentile is the heating or cooling demand level that a room’s load meets or exceeds for 98% of its annual hours of operation — essentially, a check on the worst reasonably-expected conditions in that zone, not the average. Under NCC Section J’s Part J1, this requirement specifies that this peak-end demand in the proposed building stays within a set margin of the same figure in the reference building, calculated zone by zone rather than for the building as a whole.
How the 98th Percentile Rule Changes J1V3 Modelling
Under NCC Section J, this process previously compared a proposed building’s annual greenhouse gas emissions and thermal comfort against a reference building as whole-building totals. This new layer adds a second, more granular check: it doesn’t just check whether the totals stack up, it checks whether any individual zone is quietly performing far worse than the reference building, even if the overall building average still looks compliant. A design that passed comfortably under NCC 2022 J1V3 modelling could now fail if a handful of zones — a poorly shaded west-facing office, for example — blow out at this threshold.

Climate Zone Thresholds: 120% vs 110%
Under NCC Section J, the allowable margin depends on climate zone. In climate zones 2 to 7 — covering Melbourne, Sydney, and most of Australia’s populated areas — the 98th percentile zone heating and cooling load must not exceed 120% of the reference building’s load, across 95% of the assessable floor area. In climate zone 1 (the hottest zone), the 98th percentile cooling load must stay within 110% of the reference building. In climate zone 8 (the coldest zone), the same 110% margin applies to heating load. Minimum thresholds also apply — 10 W/m² for heating and 40 W/m² for cooling — so very low-demand zones aren’t unfairly penalised by the percentage check.
Mandatory Solar PV in the Reference Building
For commercial buildings, a second major shift under NCC 2025 is that the reference building itself must now include solar PV — 225 W/m² of panel capacity across 100% of its available roof area, a requirement that didn’t exist under NCC 2022. Because the reference building sets a higher bar for on-site renewable generation, it’s harder for a proposed commercial building to offset a weaker building fabric or less efficient services simply by adding solar. The fabric and services now have to do more of the genuine work.
Perimeter and Central Zone Separation
For spaces larger than 20 m², assessors must now separate perimeter zones — areas within 45 degrees of the building’s external façade orientation — from central zones, rather than averaging heating and cooling demand across the whole floor plate. This is designed to stop poor-performing perimeter areas being masked by better-performing internal zones when the numbers are combined, which is exactly the kind of averaging effect this new check is meant to close off.
Will Existing J1V3 Models Still Comply?
Not automatically. A J1V3 model built and approved under NCC 2022 was assessed on whole-building annual emissions and comfort totals, without a zone-level check of this kind and without a mandatory-solar reference building. Re-running that same design under NCC 2025’s J1V3 modelling rules can produce a different result, particularly for commercial buildings with uneven glazing, shading, or HVAC zoning. Projects still in the design phase, or those planning to lodge after their state’s NCC 2025 adoption date, should have their J1V3 modelling re-checked against the new criteria rather than assuming an NCC 2022 pass still holds.
When Does the 98th Percentile Rule Apply to Your Project?
Because NCC 2025 adoption is state-by-state, the 98th percentile rule doesn’t apply uniformly across Australia yet. Victoria, Western Australia and the ACT adopted NCC 2025 from 1 May 2026, so the rule already applies to new commercial buildings and common areas of Class 2 buildings in those states, subject to each state’s own transition arrangements. New South Wales and Queensland have deferred mandatory adoption to 1 May 2027, though early voluntary adoption is available. South Australia has adopted only the Plumbing Code so far, with its Building Code — and therefore NCC Section J — deferred to 1 May 2027. Tasmania has paused adoption pending state legislation, and the Northern Territory reversed its earlier adoption decision, so NCC 2022 continues to apply there for now. Always confirm the current position with your state or territory building authority before lodging.

What Commercial Projects Should Do Now
For commercial buildings heading toward J1V3 modelling, the practical step is to model against this new requirement early, rather than waiting to find out at certification stage. Pay particular attention to perimeter zones with heavy glazing or west-facing exposure, since these are the areas most likely to breach this threshold even when the whole-building average still looks fine. Where a state hasn’t yet mandated NCC 2025, it’s still worth stress-testing a design against the new criteria if construction is likely to extend past the state’s adoption date.
Final Thoughts
This new rule is one of the more consequential technical changes in NCC 2025 for commercial buildings, because it targets the kind of zone-level weak spots that whole-building averages have always been able to hide. Anyone relying on J1V3 modelling for a new commercial project should treat this as a genuine design constraint, not a paperwork formality. Torple’s NCC Section J and J1V3 assessment service can model a design against this new requirement and the current NCC Section J requirements for your state. For the official Performance Requirements, see NCC Section J on ncc.abcb.gov.au, and for confirmed state adoption dates, see the ABCB’s NCC 2025 adoption page.
FAQS
It’s a new J1V3 compliance check that limits how far a proposed commercial building’s zone-level heating and cooling loads, at the demanding 98th percentile of annual hours, can exceed those of the reference building — on top of the existing whole-building emissions and comfort checks.
Whole-building averages could mask individual zones performing well below the reference building’s standard. This check closes that gap by checking zone-by-zone performance at the point where heating and cooling demand is highest, not just the annual total.
Yes, but the allowable margin varies. Climate zones 2 to 7 allow up to 120% of the reference building’s load; climate zone 1 caps cooling load at 110%, and climate zone 8 caps heating load at 110% — both across 95% of the assessable floor area.
Not automatically. Models built under NCC 2022 weren’t assessed against the 98th percentile rule or the new mandatory-solar reference building, so designs — especially those with uneven glazing or shading — should be re-checked under NCC 2025’s current criteria before assuming compliance.
It follows each state’s NCC 2025 adoption date. It already applies to commercial buildings in Victoria, WA and the ACT (from 1 May 2026), while NSW, Queensland and SA’s Building Code are deferred to 1 May 2027, and Tasmania and the NT remain on NCC 2022 for now.